APS Training Manual

DRAWING ONE If charged with the responsibility of manually controlling the multizone fan system illustrated in drawing one, what considerations exist? (1) What are you required to achieve? -(A)- A healthy living environment for occupants where the supply air is being directed. -(B)- A comfortable environment in the same location. -(C)- The most efficient energy performance. (2)What components do you have to achieve your desired results? What are the functions of each of the components? -(A)- A supply air fan and a return air fan. The function is to force the supply air into and draw the return air from the occupied space. -(B)- A heating source controlled via a manual heating valve. The function is to provide heat to the system at varying quantities. -(C)- A mechanical cooling source controlled via a manual cooling valve. The function is to provide mechanical cooling at varying quantities. -(D)- Manual zone mixing dampers enabling you to blend the hot deck air and the cold deck air. The function is to satisfy individual zone thermal requirements. -(E)- Manual dampers enabling your selection of fresh air to varying degrees and rejecting air from the building to varying degrees. The function is two fold. -1- Provide at least minimum ventilation based on the greater demand of either the building code relating to human occupancy or provide exhaust air replacement relating to building operations. -2- Provide ventilation in excess of minimum ventilation requirements to achieve cooling when the outside air provides cooling benefit. 8.81