SECOND RECHARGE CYCLE The linkage pushes PB3 closed to energize V2. This establishes the flow pattern illustrated on this drawing. The 1% of the fluid that was forced from the displacement cylinder into the cushion tank is forced back into the displacement cylinder from the cushion tank. When the displacement cylinder is completely refilled, the linkage of the displacement cylinder pushes PB1 closed and the cycle repeats. NOTE: The linkage is not mechanically connected to the diamond shaped actuator; therefore, there will be a temporary gap between them during the second recharging stage. H L S H L S 120V 24V CR1 CUSHION TANK VALVE PRV HIGH PRESSURE AIR DEPRESSURIZATION ACTUATOR V3 V4 V5 C NC NC NO NO NO PB3 PB2 CR1 V1 NC V2 C NC NO PB1 DISPLACEMENT ACTUATOR DIAMOND- SHAPED ACTUATOR VALVE LINKAGE RETURN SPRING RETURN SPRING 1 2 4 PB1 2 V1 4 2 V3 4 2 V4 4 2 V5 4 1 3 3 V2 4 1 5 5 2 CR1-1 PB2 PB3 ENERGIZED DE-ENERGIZED PRESSURE TRANSMITTER TO LOGGER PRESSURE TRANSMITTER NOTE; PB1, PB2 AND PB3 ARE MOMENTARY PUSH BUTTONS. PB2 IS NORMALLY CLOSED. PB1 AND PB3 ARE NORMALLY OPEN. 13.297