The Thermostat Lied

Training Manual
Quick Links
Recent Posts

DX Cooling Opportunity

HVAC systems that mix fresh air and building return air to varying quantities for cooling purposes often have control logic comparing the total heat content of the outdoor to the total heat content of the return air.

Read More »
Recent Videos

The Retrofit That Made Things Worse

Induction units were already not winning any efficiency awards. Then came the BAS upgrades — and two mistakes that made a flawed system perform even worse. We found them in the field. This is what we saw.

Read More »

The Cure That May Have Made Things Worse

Some HVAC measures mandated for COVID and Legionnaires’ disease may have increased the very risks they were designed to prevent. The evidence didn’t always support the mandate. This video examines what the data actually shows — and what better alternatives look like.

Read More »
Questions?
The Thermostat Lied (And Your Energy Bill Told the Truth)
VAV boxes provide cooling and a heating coil in harmony, with both functions controlled by a single thermostat. When the heating valve no longer seats properly, unwanted heat continuously enters the airstream. The thermostat automatically responds by increasing cooling to maintain the desired room temperature. As a result, occupants remain comfortable while energy is wasted through simultaneous heating and cooling—a problem that often goes unnoticed because the control system masks the inefficiency.